A feeder supplies two three-phase, 460 V motors: 20 HP (FLC 27 A) and 10 HP (FLC 14 A). Per NEC 430.24, what minimum feeder conductor ampacity is required?

a.41 A
b.51.25 A
c.54 A
d.47.75 A

Explanation

NEC 430.24 requires 125% of the largest motor's FLC plus the sum of the others: (27 x 1.25) + 14 = 33.75 + 14 = 47.75 A. 41 A omits the 125% factor, 51.25 A applies 125% to both, and 54 A doubles the largest.

Law Reference: 2023 NEC §430.24