A 45 kVA, three-phase transformer has a 208 V secondary. What is the rated secondary current?

a.125 A
b.108 A
c.216 A
d.150 A

Explanation

For three-phase, I = VA / (1.732 x V) = 45,000 / (1.732 x 208) = 45,000 / 360 = about 125 A. Dividing by 208 alone (216 A) ignores the sqrt(3) factor, and the other values use wrong voltages.