Equipment & SystemsQuestion 265 of 521
A 45 kVA, three-phase transformer has a 208 V secondary. What is the rated secondary current?
a.125 A
b.108 A
c.216 A
d.150 A
Explanation
For three-phase, I = VA / (1.732 x V) = 45,000 / (1.732 x 208) = 45,000 / 360 = about 125 A. Dividing by 208 alone (216 A) ignores the sqrt(3) factor, and the other values use wrong voltages.
Practice all 521 questions free — no signup required.
Related questions on this topic
- A 30 kVA, three-phase transformer has a 480 V primary (primary current ~36 A). With primary-only protection and no supervised condition, what is the maximum primary overcurrent device using the 125% factor of Table 450.3(B)?
- NEC 450.3(B) overcurrent protection percentages for transformers 1000 V or less are based on what?
- What is the rated primary current of a 25 kVA, single-phase transformer with a 240 V primary?
- Why must a motor circuit have both overload protection AND short-circuit/ground-fault protection?
- A 30 HP, 460 V, three-phase motor has an FLC of 40 A. What is the minimum ampere rating of the motor disconnecting means (115% of FLC)?
- Under NEC 430.102(B), where must the disconnecting means for a motor generally be located?