NEC 450.3(B) overcurrent protection percentages for transformers 1000 V or less are based on what?

a.The secondary conductor ampacity
b.The connected load kVA
c.The rated primary (and where applicable secondary) current of the transformer
d.The available fault current

Explanation

Table 450.3(B) percentages (e.g., 125%, 167%, 250%, 300%) are applied to the transformer's rated primary or secondary current, not the load or fault current. This protects the transformer itself; separate rules protect the secondary conductors.

Law Reference: 2023 NEC §450.3