Equipment & SystemsQuestion 261 of 521
If a motor-compressor (rated-load 18 A) will not start on the 175% device, NEC 440.22(A) permits increasing the protection to a maximum of what value?
a.225% = 40.5 A
b.200% = 36 A
c.250% = 45 A
d.300% = 54 A
Explanation
NEC 440.22(A) allows an increase up to 225% of the rated-load current where the 175% device will not carry starting current: 18 x 2.25 = 40.5 A. 200%, 250%, and 300% are not the permitted ceilings for hermetic-compressor branch-circuit protection.
Law Reference: 2023 NEC §440.22Practice all 521 questions free — no signup required.
Related questions on this topic
- The 'Maximum Overcurrent Protective Device' (MOCP or 'Max Fuse/HACR Breaker') rating on an HVAC nameplate specifies what?
- An A/C condensing unit has a compressor rated-load current of 18 A and a fan motor of 2 A. Using the 125%-of-largest-motor-plus-others method, what is the minimum circuit ampacity (MCA)?
- For a hermetic motor-compressor with a rated-load current of 18 A, what is the maximum branch-circuit short-circuit/ground-fault protective device, based on the 175% value of NEC 440.22(A)?
- A 30 kVA, three-phase transformer has a 480 V primary (primary current ~36 A). With primary-only protection and no supervised condition, what is the maximum primary overcurrent device using the 125% factor of Table 450.3(B)?
- NEC 450.3(B) overcurrent protection percentages for transformers 1000 V or less are based on what?
- What is the rated primary current of a 25 kVA, single-phase transformer with a 240 V primary?