Equipment & SystemsQuestion 259 of 521
An A/C condensing unit has a compressor rated-load current of 18 A and a fan motor of 2 A. Using the 125%-of-largest-motor-plus-others method, what is the minimum circuit ampacity (MCA)?
a.20 A
b.25 A
c.24.5 A
d.27.5 A
Explanation
MCA = 125% of the largest motor + sum of the other loads: (18 x 1.25) + 2 = 22.5 + 2 = 24.5 A. 20 A omits the 125% factor, 25 A applies 125% to the whole 20 A, and 27.5 A applies 125% to both loads.
Law Reference: 2023 NEC §440.33Practice all 521 questions free — no signup required.
Related questions on this topic
- A single hermetic refrigerant motor-compressor has a rated-load current of 24 A. Per NEC 440.32, what minimum branch-circuit conductor ampacity is required?
- On an air-conditioning unit nameplate, what does the 'Minimum Circuit Ampacity (MCA)' value tell the installer?
- The 'Maximum Overcurrent Protective Device' (MOCP or 'Max Fuse/HACR Breaker') rating on an HVAC nameplate specifies what?
- For a hermetic motor-compressor with a rated-load current of 18 A, what is the maximum branch-circuit short-circuit/ground-fault protective device, based on the 175% value of NEC 440.22(A)?
- If a motor-compressor (rated-load 18 A) will not start on the 175% device, NEC 440.22(A) permits increasing the protection to a maximum of what value?
- A 30 kVA, three-phase transformer has a 480 V primary (primary current ~36 A). With primary-only protection and no supervised condition, what is the maximum primary overcurrent device using the 125% factor of Table 450.3(B)?