A single hermetic refrigerant motor-compressor has a rated-load current of 24 A. Per NEC 440.32, what minimum branch-circuit conductor ampacity is required?

a.24 A
b.26 A
c.28.8 A
d.30 A

Explanation

NEC 440.32 requires conductors for a single motor-compressor to be sized at 125% of the rated-load current or branch-circuit selection current, whichever is larger: 24 x 1.25 = 30 A. 24 A omits the factor, 26 A is ~108%, and 28.8 A is 120%.

Law Reference: 2023 NEC §440.32