Equipment & SystemsQuestion 258 of 521

The 'Maximum Overcurrent Protective Device' (MOCP or 'Max Fuse/HACR Breaker') rating on an HVAC nameplate specifies what?

a.The smallest breaker that will start the unit
b.The largest fuse or circuit breaker permitted to protect the branch circuit
c.The required conductor size
d.The disconnect switch rating only

Explanation

The MOCP is the maximum size of fuse or HACR-rated breaker allowed for the unit's branch circuit; you may install this size or smaller, but not larger. MCA sets the conductor ampacity; the two values are used together per 440.4(B).

Law Reference: 2023 NEC §440.4