For the 7.5 HP, 230 V motor (FLC 22 A), what minimum branch-circuit conductor ampacity is required by NEC 430.22?
a.22 A
b.24.2 A
c.25.3 A
d.27.5 A
Explanation
125% of FLC: 22 x 1.25 = 27.5 A. 22 A omits the factor, 24.2 A is 110%, and 25.3 A is 115%.
Law Reference: 2023 NEC §430.22Practice all 521 questions free — no signup required.
Related questions on this topic
- Per NEC 430.62, the maximum feeder overcurrent device for several motors equals the largest branch-circuit protective device rating plus the sum of the other motors' FLCs. If the largest motor's branch device is 90 A and the other motors' FLCs total 35 A, what is the maximum feeder device?
- The equipment grounding conductor for a motor branch circuit is sized based on what, per NEC 250.122?
- Per NEC Table 430.250, what is the full-load current of a 7.5 HP, 230 V, three-phase motor?
- For the 7.5 HP, 230 V motor (FLC 22 A), what is the maximum nontime-delay fuse per Table 430.52 (300%)?
- When the Table 430.52 percentage produces a value that does not correspond to a standard fuse or breaker size, NEC 430.52(C)(1) Exception No. 1 permits you to:
- Per NEC Table 430.248, what is the full-load current of a 1 HP, single-phase, 115 V motor?