Equipment & SystemsQuestion 293 of 521
For the 7.5 HP, 230 V motor (FLC 22 A), what is the maximum nontime-delay fuse per Table 430.52 (300%)?
a.66 A
b.55 A
c.38.5 A
d.176 A
Explanation
Nontime-delay fuse: 300% of FLC = 22 x 3.00 = 66 A. 55 A is 250% (inverse-time breaker), 38.5 A is 175% (dual-element fuse), and 176 A is 800% (instantaneous trip).
Law Reference: 2023 NEC §430.52Practice all 521 questions free — no signup required.
Related questions on this topic
- The equipment grounding conductor for a motor branch circuit is sized based on what, per NEC 250.122?
- Per NEC Table 430.250, what is the full-load current of a 7.5 HP, 230 V, three-phase motor?
- For the 7.5 HP, 230 V motor (FLC 22 A), what minimum branch-circuit conductor ampacity is required by NEC 430.22?
- When the Table 430.52 percentage produces a value that does not correspond to a standard fuse or breaker size, NEC 430.52(C)(1) Exception No. 1 permits you to:
- Per NEC Table 430.248, what is the full-load current of a 1 HP, single-phase, 115 V motor?
- A small single-phase motor has a nameplate FLA of 14 A, service factor 1.0, no marked temperature rise. What is the maximum overload device rating under NEC 430.32(A)(1)?