Rapid shutdown requires that controlled conductors more than 1 foot outside the array boundary be limited to what within 30 seconds?

a.80 volts within 10 seconds
b.30 volts within 30 seconds
c.50 volts within 1 minute
d.0 volts instantly

Explanation

Section 690.12 requires that conductors leaving the array boundary be reduced to no more than 30 volts within 30 seconds of rapid-shutdown initiation. This protects firefighters and responders; the 80-volt limit applies only inside the array boundary, not to the outside conductors.

Law Reference: 2023 NEC §690.12