A storage-battery emergency source must be capable of maintaining the total emergency load for what minimum time and voltage?

a.30 minutes at 80% of nominal
b.1 hour at 90% of nominal
c.2 hours at 100% of nominal
d.1 1/2 hours at not less than 87 1/2% of nominal voltage

Explanation

Section 700.12 requires a storage battery serving as an emergency source to maintain the total load for a minimum of 1 1/2 hours without the voltage falling below 87 1/2 percent of nominal. Shorter durations or lower voltage thresholds do not meet the emergency-source requirement.

Law Reference: 2023 NEC §700.12