Equipment & SystemsQuestion 329 of 521
Under the busbar interconnection rule, the sum of the main utility overcurrent device plus the inverter (power-production) overcurrent device generally may not exceed what percent of the busbar rating?
a.120% of the busbar ampacity
b.100% of the busbar ampacity
c.150% of the busbar ampacity
d.80% of the busbar ampacity
Explanation
Section 705.12(B)(3) allows the sum of the ampere ratings of the main supply overcurrent device and the power-production (inverter) overcurrent device to be up to 120 percent of the busbar rating when the inverter breaker is at the opposite end from the main. Exceeding 120 percent would risk overloading the busbar.
Law Reference: 2023 NEC §705.12Practice all 521 questions free — no signup required.