How must Class 2 conductors generally be separated from electric light and power conductors?

a.They may be freely mixed with 480 V conductors
b.6 inches with no exceptions
c.12 inches always
d.At least 2 inches from power conductors unless a permitted separation method is used

Explanation

Section 725.136 generally requires Class 2 conductors to be separated at least 2 inches from conductors of electric light, power, and Class 1 circuits, unless one of the permitted separation methods (such as a barrier or listed cable) is used. Freely mixing them in a raceway or enclosure with power conductors is not allowed.

Law Reference: 2023 NEC §725.136