When is a primary protector required on a communications circuit?
a.Never required
b.Where the circuit is exposed to lightning or to accidental contact with power conductors over 300 V to ground
c.Required only for indoor circuits
d.Required only for fiber-optic cable
Explanation
Section 805.90 requires a listed primary protector where communications circuits are exposed to accidental contact with power conductors over 300 volts to ground or are subject to lightning exposure. Fiber-optic cables carry no metallic conductors, so they do not require this electrical protector.