Equipment & SystemsQuestion 342 of 521

Low-voltage lighting systems covered by Article 411 are generally limited to what maximum voltage?

a.120 volts
b.60 volts
c.12 volts only
d.30 volts (or 15 volts where in direct contact with water)

Explanation

Section 411.7 limits low-voltage lighting systems to a maximum of 30 volts (42.4 volts peak), reduced to 15 volts (21.2 volts peak) where the luminaires are installed in wet contact such as in a fountain. The 12-volt figure is a common operating voltage but is not the code maximum.

Law Reference: 2023 NEC §411.3

Practice all 521 questions free — no signup required.

Related questions on this topic

Last reviewed: · editorial process

PrepPass Editorial Team · Verified against California CSLB C-10 Electrical Trade Examination · How we review