Services & DistributionQuestion 35 of 521
A dwelling has one 12 kW electric range. Using Table 220.55 Column C, what is the demand load?
a.12 kW
b.9.6 kW
c.8 kW
d.6 kW
Explanation
Column C of Table 220.55 gives 8 kW of demand for a single range not over 12 kW. 12 kW ignores the demand factor, and the other values misread the column.
Law Reference: 2023 NEC §220.55Practice all 521 questions free — no signup required.
Related questions on this topic
- A branch circuit carries a continuous load of 80 A. What minimum OCPD rating is required?
- Using the standard 3 VA/sq ft general lighting unit load, what is the general lighting load for a 2,000 sq ft dwelling (before demand factors)?
- A dwelling has two required small-appliance branch circuits and one laundry circuit. What is the total calculated load for these before demand factors?
- Two 12 kW electric ranges are in a two-unit dwelling. Using Table 220.55 Column C, what is the total demand?
- A single household electric clothes dryer is rated 4 kW. What value is used for the service/feeder demand calculation?
- A range has a Column C demand of 8 kW. What is the maximum neutral demand load for that range?