Services & DistributionQuestion 38 of 521

A range has a Column C demand of 8 kW. What is the maximum neutral demand load for that range?

a.5.6 kW
b.8 kW
c.4 kW
d.2.8 kW

Explanation

Per 220.61(B)(1), the feeder/service neutral load for a range may be taken at 70% of the ungrounded demand: 8 kW x 0.70 = 5.6 kW. 8 kW ignores the 70% allowance, and the other values misapply it.

Law Reference: 2023 NEC §220.61