Services & DistributionQuestion 40 of 521

A dwelling's general lighting plus small-appliance/laundry load totals 13,500 VA. Using the standard demand factors (first 3,000 VA at 100%, remainder at 35%), what is the demand?

a.4,725 VA
b.6,675 VA
c.13,500 VA
d.3,000 VA

Explanation

First 3,000 VA at 100% = 3,000 VA; remaining 10,500 VA at 35% = 3,675 VA; total = 6,675 VA. 13,500 VA ignores demand factors, and the other values misapply them.

Practice all 521 questions free — no signup required.

Related questions on this topic

Last reviewed: · editorial process

PrepPass Editorial Team · Verified against California CSLB C-10 Electrical Trade Examination · How we review
Report