Services & DistributionQuestion 43 of 521
A dwelling has 10 kW of electric heat and a 5 kW air conditioner that never run at the same time. What load is included in the calculation?
a.15 kW (both)
b.7.5 kW (average)
c.10 kW (the larger)
d.5 kW (the smaller)
Explanation
Per 220.60, for noncoincident loads only the larger of the two is included: 10 kW. Adding both (15 kW), averaging, or using the smaller misapplies the noncoincident-load rule.
Law Reference: 2023 NEC §220.60Practice all 521 questions free — no signup required.
Related questions on this topic
- A dwelling's general lighting plus small-appliance/laundry load totals 13,500 VA. Using the standard demand factors (first 3,000 VA at 100%, remainder at 35%), what is the demand?
- What is the minimum service disconnecting means rating for a one-family dwelling?
- The optional feeder/service calculation of 220.84 for a multifamily dwelling may be used only when which condition is met?
- Service-entrance conductors must supply a computed load of 160 A continuous. What minimum conductor ampacity is required per 230.42?
- What is the full-load secondary current of a 45 kVA, 3-phase, 208 V transformer?
- What is the full-load primary current of a 75 kVA, 3-phase, 480 V transformer?