Service-entrance conductors must supply a computed load of 160 A continuous. What minimum conductor ampacity is required per 230.42?

a.160 A
b.128 A
c.175 A
d.200 A

Explanation

Per 230.42(A), service conductors must have an ampacity of at least 125% of continuous load: 160 A x 1.25 = 200 A. 160 A ignores the factor, 128 A reduces the load, and 175 A is insufficient.

Law Reference: 2023 NEC §230.42