You test a 480 V motor with a 500 V megohmmeter and read 0.4 megohms. Using the common one-megohm-per-kilovolt-plus-one-megohm minimum guideline, is the insulation acceptable?
a.Yes, 0.4 megohms easily exceeds the minimum
b.Yes, any reading above 0 megohms passes
c.Cannot tell without measuring current
d.No, the reading is well below the ~1 megohm minimum, indicating degraded insulation
Explanation
A widely used field minimum is about 1 megohm (or 1 megohm per kV of rating plus 1). At 0.4 megohms the motor is far below that floor, so the insulation is suspect and the motor should not be returned to service without further evaluation. A near-zero reading trends toward a winding-to-ground fault; 'any value above 0' (b) is not a valid criterion.
Practice all 521 questions free — no signup required.
Related questions on this topic
- Before performing a continuity test on a cable with an ohmmeter, what condition must exist?
- A plug-in receptacle tester shows its 'hot/neutral reversed' indication at a 120 V outlet. What does this mean and what is the fix?
- On a 120/240 V multiwire branch circuit, the shared neutral becomes open. What symptom is most characteristic?
- Which instrument lets you measure the current in a single energized conductor without disconnecting or breaking into the circuit?
- A DMM reads 12 V across a resistor and a clamp meter reads 3 A through it. What is the resistor's value?
- A conductor run carries 10 A and the total round-trip resistance of the wire is 0.5 ohms. What is the voltage drop along the conductors?
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against California CSLB C-10 Electrical Trade Examination · How we review