Services & DistributionQuestion 87 of 521
A feeder supplies a single continuous load of 100 A. The minimum feeder conductor ampacity and overcurrent device rating is:
a.100 A
b.110 A
c.115 A
d.125 A
Explanation
For a continuous load, both the conductor ampacity and the overcurrent device must be at least 125% of the load: 100 x 1.25 = 125 A. Selecting 100 A ignores the continuous-load factor entirely, and 110 A/115 A fall short of the required 125%.
Law Reference: 2023 NEC §215.2Practice all 521 questions free — no signup required.