A feeder supplies a single continuous load of 100 A. The minimum feeder conductor ampacity and overcurrent device rating is:

a.100 A
b.110 A
c.115 A
d.125 A

Explanation

For a continuous load, both the conductor ampacity and the overcurrent device must be at least 125% of the load: 100 x 1.25 = 125 A. Selecting 100 A ignores the continuous-load factor entirely, and 110 A/115 A fall short of the required 125%.

Law Reference: 2023 NEC §215.2