Services & DistributionQuestion 90 of 521

Ground-fault protection of equipment is generally required for solidly grounded wye services of more than 150 V to ground but not exceeding 1000 V phase-to-phase, where the service disconnect is rated:

a.1000 A or more
b.400 A or more
c.100 A or more
d.2000 A or more

Explanation

Per 230.95, ground-fault protection of equipment is required on such services where the service disconnecting means is rated 1000 A or more. The other ampere thresholds do not match the code trigger for this GFP requirement.

Law Reference: 2023 NEC §230.95