Gas PipingQuestion 262 of 360
Which installation practice for a flexible appliance connector is correct?
a.Keep it accessible and in the open, not concealed in a wall or behind an immovable appliance
b.Cut it to length and re-flare the ends on site
c.Reuse the old connector from the previous appliance
d.Bury it in the slab for a clean look
Explanation
An appliance connector must stay accessible and out in the open for inspection and service, not concealed inside a wall or trapped behind an appliance that cannot be moved. Connectors are factory assemblies that are not cut or re-flared in the field, and a new connector should be used rather than reusing an old one. These rules reduce the chance of an undetected leak.
Practice all 360 questions free — no signup required.
Related questions on this topic
- Why is it important to know that propane (LP) vapor is heavier than air when installing gas piping and appliances?
- Compared with propane, how does natural gas behave if it leaks indoors?
- A sizing table (natural gas) shows 1/2-inch pipe carries 92 cfh and 3/4-inch pipe carries 190 cfh at the governing length. A section supplies a 40,000 BTU/hr wall furnace plus a 45,000 BTU/hr water heater. What is the smallest size that works?
- Why must horizontal and vertical gas piping be supported at the intervals required by code?
- An older flexible connector is found kinked and corroded when a water heater is replaced. What is the correct action?
- Gas piping must pass through a concrete slab. What is the correct approach?