Theory & SafetyQuestion 113 of 120
A balanced delta-connected load has a phase current of 20 amperes. What is the line current?
a.20 amperes
b.Approximately 34.6 amperes
c.Approximately 11.5 amperes
d.60 amperes
Explanation
In a delta connection each line conductor feeds two phase windings, so line current equals 1.732 times phase current: 20 x 1.732 = 34.6 amperes. The 20-ampere answer describes a wye connection, 11.5 amperes divides instead of multiplying, and 60 amperes triples the value rather than applying the square root of three.
Practice all 120 questions free — no signup required.
Related questions on this topic
- A 20-ohm resistor and a 30-ohm resistor are connected in parallel. What is the total resistance?
- A balanced three-phase load draws 40 amperes at 480 volts with a power factor of 0.85. What is the true power?
- On a 208Y/120-volt wye system, what is the relationship between line voltage and phase voltage?
- A single-phase transformer has a 480-volt primary and a 120-volt secondary. If the secondary carries 100 amperes, what is the approximate primary current?
- What is the secondary full-load current of a 25 kVA single-phase transformer with a 240-volt secondary?
- A 480-volt panelboard is mounted on a wall with a grounded concrete wall directly behind the working space. What is the minimum depth of working space?