Theory & SafetyQuestion 120 of 120
Which sequence correctly describes verifying that equipment is de-energized before beginning work?
a.Test the meter on a known live source, test the de-energized conductors, then retest the meter on the known live source
b.Test the de-energized conductors, then test the meter on a known live source
c.Rely on the open position of the disconnect and the applied lock
d.Test the de-energized conductors only, since the meter was checked at the start of the shift
Explanation
The live-dead-live method proves the instrument is working both before and after the absence-of-voltage test, so a meter that failed during the check cannot lead a worker to treat energized conductors as safe. Locking and tagging the disconnect is required, but it does not by itself confirm that the conductors ahead of the work are actually de-energized, since backfeeds and mislabeled circuits are common.
Practice all 120 questions free — no signup required.
Related questions on this topic
- A single-phase transformer has a 480-volt primary and a 120-volt secondary. If the secondary carries 100 amperes, what is the approximate primary current?
- What is the secondary full-load current of a 25 kVA single-phase transformer with a 240-volt secondary?
- A 480-volt panelboard is mounted on a wall with a grounded concrete wall directly behind the working space. What is the minimum depth of working space?
- What is the minimum width of working space in front of electrical equipment?
- Entrances at each end of the working space are generally required for equipment rated at least what value and over 6 feet wide?
- The dedicated equipment space above a panelboard extends from the top of the equipment to what height?