Services, Grounding & BondingQuestion 44 of 120
What is the secondary full-load current of a 75 kVA transformer with a 208Y/120-volt, three-phase secondary?
a.120 amperes
b.361 amperes
c.208 amperes
d.104 amperes
Explanation
Secondary current is I = VA / (1.732 x E) = 75,000 / (1.732 x 208) = 75,000 / 360.3, or about 208 amperes. The 361-ampere answer divides by the voltage alone, 120 amperes uses the phase voltage incorrectly, and 104 amperes is roughly half the correct value.
Practice all 120 questions free — no signup required.
Related questions on this topic
- Service-entrance conductors supply 68 amperes of continuous load plus 120 amperes of noncontinuous load. What minimum ampacity must the conductors have?
- Using the dwelling conductor table, what is the minimum copper conductor size for a 400-ampere single-phase dwelling service?
- A 45 kVA, three-phase transformer has a 480-volt primary. If only primary overcurrent protection is provided at 125 percent, what is the maximum standard primary device rating?
- What is the minimum length of a rod-type grounding electrode?
- Where two rod electrodes are installed to make up the grounding electrode system, what is the minimum spacing between them?
- A single ground rod does not have to be supplemented by a second electrode if its resistance to earth does not exceed what value?