Services, Grounding & BondingQuestion 51 of 120
What is the maximum number of service disconnecting means permitted for a single set of service-entrance conductors?
a.Eight
b.Two
c.Four
d.Six
Explanation
Up to six service disconnects are permitted, but current code requires them to be in separate enclosures or in a listed assembly with individual disconnects, each marked as a service disconnect. Two and four are below the ceiling but are not the code maximum, and eight exceeds the limit.
Law Reference: 2023 NEC §230.71Practice all 120 questions free — no signup required.