Branch Circuits & FeedersQuestion 6 of 120
A 480-volt, three-phase feeder carries 40 amperes 250 feet using 6 AWG copper (26,240 circular mils). Using K = 12.9, what is the approximate voltage drop?
a.14.8 volts
b.4.9 volts
c.8.5 volts
d.17.0 volts
Explanation
For three-phase, VD = (1.732 x K x I x L) / CM = (1.732 x 12.9 x 40 x 250) / 26,240, or about 8.5 volts, roughly 1.8 percent of 480 volts. The 17.0-volt answer uses the single-phase factor of 2 instead of 1.732, 4.9 volts halves the run length, and 14.8 volts does not follow from the given values.
Law Reference: 2023 NEC Chapter 9, Table 8Practice all 120 questions free — no signup required.
Related questions on this topic
- Six current-carrying 12 AWG THHN copper conductors are installed in a single EMT run at a 30 degrees C ambient. What is the adjusted ampacity of each conductor before termination limits are applied?
- Four current-carrying 8 AWG THWN-2 copper conductors run in a raceway through a 48 degrees C ambient. What is the adjusted ampacity of each conductor?
- A 120-volt circuit carries 20 amperes through 12 AWG copper (6,530 circular mils) to a load 100 feet away. Using K = 12.9, what is the approximate voltage drop?
- A 120-volt branch circuit must carry 12 amperes 120 feet with voltage drop held to 3 percent. Using K = 12.9 for copper, what is the smallest conductor that meets the target?
- A feeder supplies 30 amperes of continuous load plus 50 amperes of noncontinuous load. What is the minimum standard overcurrent device rating?
- Which of the following is NOT a standard ampere rating for fuses and inverse-time circuit breakers?
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against Journeyman Electrician Licensing Exam (NEC-based) · How we review