Drainage, Waste & VentQuestion 13 of 120
Which fitting is required to change direction from horizontal to horizontal in a drainage line?
a.A short sweep quarter bend
b.A sanitary tee
c.A combination wye and 1/8 bend
d.A vent tee
Explanation
A horizontal-to-horizontal change of direction must use a long sweep pattern such as a combination wye and 1/8 bend, which keeps the flow moving without a sharp shoulder where solids collect. A short sweep quarter bend turns too abruptly for horizontal flow, a sanitary tee is only for horizontal-to-vertical, and a vent tee is a dry vent fitting not rated for drainage flow.
Practice all 120 questions free — no signup required.
Related questions on this topic
- A vent terminal passes through a roof that is used only for weather protection in an area with no snow-depth requirement. What is the minimum height the vent must extend above the roof surface?
- A vent terminal must be located away from an openable window. Which arrangement satisfies the code?
- Which fitting is acceptable for changing direction from horizontal to vertical in a drainage line?
- A 4 in horizontal building drain runs 340 ft under a warehouse slab. Not counting the cleanout at the upstream end of the run, what is the minimum number of additional cleanouts required for spacing alone?
- A cleanout is installed on a 2 in horizontal waste line in a finished room. What is the minimum clearance required in front of the cleanout?
- A 6 in horizontal drainage line requires a cleanout. What is the minimum size of the cleanout opening?