Water Supply & DistributionQuestion 35 of 120

A potable water supply outlet discharges over a receptor and the effective opening of the outlet is 1 in. What is the minimum required air gap?

a.1 in
b.1-1/2 in
c.3 in
d.2 in

Explanation

The air gap must be at least twice the diameter of the effective opening, so 2 x 1 in = 2 in. The 1 in answer is only the code minimum floor that applies to very small openings, not the calculated value here. The 1-1/2 in choice uses a 1.5 multiplier and 3 in uses a 3x multiplier, neither of which the code uses.

Law Reference: UPC §603.3.1