Water Supply & DistributionQuestion 50 of 120
What is the maximum weighted average lead content permitted on the wetted surfaces of pipe, fittings, and fixtures used to convey water for human consumption?
a.0.2 percent
b.0.05 percent
c.0.25 percent
d.8 percent
Explanation
The lead-free standard limits the wetted surfaces to a weighted average of not more than 0.25 percent lead. The 0.2 percent value is the separate limit that applies to solder and flux, not to the wetted surfaces of the components. The 0.05 percent figure is stricter than the code requires, and 8 percent describes older leaded brass that may no longer be installed in potable systems.
Practice all 120 questions free — no signup required.
Related questions on this topic
- Which condition makes a pressure vacuum breaker an unacceptable choice for a given cross-connection?
- Which copper tube designation has the heaviest wall thickness and is the type commonly required for an underground water service?
- What is the maximum lead content permitted in solder and flux used on a potable water piping system?
- Static pressure at the main is 72 psi. Meter loss at design flow is 9 psi, the highest fixture is 26 ft above the meter, and 15 psi residual is required at that fixture. How much pressure is available to overcome friction loss in the piping?
- A flushometer water closet on the top floor requires 20 psi residual. Static pressure is 65 psi, combined meter and backflow preventer loss is 10 psi, and the flush valve is 34 ft above the meter. How much pressure remains for friction loss in the piping and fittings?
- A sizing problem leaves 24 psi available for friction loss. The measured developed length to the most remote fixture is 160 ft, and fittings are estimated to add 50 percent to that length. What is the allowable friction loss per 100 ft of pipe?
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against Journeyman Plumber Licensing Exam (UPC/IPC-based) · How we review