Gas PipingQuestion 87 of 120

A natural gas system runs from the meter through section A (12 ft), then section B (18 ft), then section C (35 ft) to the farthest appliance. Using the longest developed length method, which length is used to select the size of section A?

a.12 ft, the actual length of section A
b.30 ft, the length from the meter through section B
c.23 ft, the average of the three sections
d.65 ft, the total length from the meter to the farthest outlet

Explanation

The longest length method sizes every section of the system from the single length column that corresponds to the distance from the point of supply to the most remote outlet, here 12 + 18 + 35 = 65 ft. Using 12 ft or 30 ft applies a section length rather than the developed length to the farthest outlet and undersizes the pipe; averaging section lengths is not a recognized method.

Law Reference: IFGC §402.4