CSLB General Building (B) — All Questions
← Back to practice18 questions
A load draws 80 kW of real power and 100 kVA of apparent power. What is the power factor?
- a.1.0
- b.0.8✓
- c.0.6
- d.0.9
Power factor = real power / apparent power = 80 kW / 100 kVA = 0.8.
For a load of 80 kW real and 100 kVA apparent, what is the reactive power?
- a.80 kVAR
- b.100 kVAR
- c.60 kVAR✓
- d.40 kVAR
Reactive power = sqrt(kVA^2 - kW^2) = sqrt(100^2 - 80^2) = sqrt(3,600) = 60 kVAR.
What is the real power of a three-phase load at 480 V, 50 A, and 0.85 power factor?
- a.24,960 W
- b.41,568 W
- c.30,000 W
- d.35,326 W✓
P = 1.732 x V x I x PF = 1.732 x 480 x 50 x 0.85 = 35,326 W.
In a balanced wye (star) three-phase system, the line current is:
- a.Equal to the phase current✓
- b.1.732 times the phase current
- c.0.577 times the phase current
- d.2 times the phase current
In a wye connection the same conductor carries phase and line current, so line current equals phase current.
In a balanced delta three-phase system, the line current equals:
- a.The phase current
- b.1.732 times the phase current✓
- c.0.577 times the phase current
- d.3 times the phase current
In a delta connection the line current is the square root of 3 (1.732) times the phase (winding) current.
In a 208Y/120-V wye system, what is the phase (line-to-neutral) voltage?
- a.208 V
- b.240 V
- c.120 V✓
- d.277 V
Line-to-neutral voltage = line-to-line / 1.732 = 208 / 1.732 = 120 V.
In a 480Y/277-V system, what is the line-to-neutral voltage?
- a.120 V
- b.240 V
- c.208 V
- d.277 V✓
Line-to-neutral = 480 / 1.732 = 277 V.
An 80-kW load at 0.80 power factor is to be corrected to 0.95. How many kVAR of capacitance are required (tan 36.87 = 0.75, tan 18.19 = 0.329)?
- a.33.7 kVAR✓
- b.60 kVAR
- c.48 kVAR
- d.20 kVAR
Qc = kW x (tan(theta1) - tan(theta2)) = 80 x (0.750 - 0.329) = 80 x 0.421 = 33.7 kVAR.
In a three-phase, four-wire wye system serving nonlinear loads, which harmonic order adds arithmetically in the neutral?
- a.2nd
- b.3rd✓
- c.5th
- d.7th
Triplen harmonics, principally the 3rd, are in phase across all three phases and add in the neutral rather than canceling.
On a feeder with significant harmonic (nonlinear) load, the neutral conductor is treated as:
- a.Not a current-carrying conductor
- b.A half current-carrying conductor
- c.A current-carrying conductor✓
- d.An ignored conductor
Where the major portion of the load is nonlinear, the neutral carries harmonic current and must be counted as a current-carrying conductor for adjustment.2023 NEC 310.15(E)
A three-phase panel has phase loads of A = 40 A, B = 30 A, C = 20 A. What is the ideal balanced current per phase?
- a.40 A
- b.20 A
- c.25 A
- d.30 A✓
Total = 40 + 30 + 20 = 90 A; balanced across three phases = 90 / 3 = 30 A per phase.
A single-line (one-line) diagram represents an electrical system by:
- a.One line for each circuit or set of conductors✓
- b.Each individual conductor drawn separately
- c.The physical layout of raceways
- d.Only the branch-circuit wiring
A one-line diagram uses a single line and standard symbols to represent circuits and equipment, simplifying analysis of the power system.
A transformer steps 480 V down to 120 V. What is its turns (voltage) ratio?
- a.2:1
- b.4:1✓
- c.1:4
- d.8:1
Turns ratio = primary voltage / secondary voltage = 480 / 120 = 4:1.
A transformer has a 4:1 turns ratio and a 10-A primary current. What is the secondary current (ideal)?
- a.10 A
- b.2.5 A
- c.40 A✓
- d.20 A
Current is inversely proportional to the turns ratio: Is = Ip x (Np/Ns) = 10 x 4 = 40 A.
An AC circuit at 240 V draws 12 A. What is the circuit impedance?
- a.2 ohms
- b.0.05 ohms
- c.288 ohms
- d.20 ohms✓
By Ohm's law for AC, Z = V / I = 240 / 12 = 20 ohms.
A continuous load draws 40 A. At what minimum ampacity must the branch-circuit conductors and overcurrent device be rated?
- a.50 A✓
- b.40 A
- c.32 A
- d.45 A
Continuous loads require 125% sizing: 40 A x 1.25 = 50 A for the conductors and overcurrent device.2023 NEC 210.20(A)
The demand factor of a system is defined as:
- a.A value always greater than 1
- b.Maximum demand divided by total connected load✓
- c.Connected load divided by maximum demand
- d.Always equal to 1
Demand factor = maximum demand / total connected load; it is 1 or less and reflects load diversity.
What are the commonly recommended maximum voltage-drop limits for a branch circuit and for the combined feeder plus branch circuit?
- a.5% and 8%
- b.2% and 4%
- c.3% and 5%✓
- d.1% and 3%
The informational recommendation is 3% maximum on a branch circuit and 5% maximum for feeder plus branch circuit combined.