A #3 Cu THHN conductor has a 90 C ampacity of 110 A. In a 50 C ambient (correction factor 0.82), what is the corrected ampacity?
a.110 A
b.100 A
c.90 A
d.82 A
Explanation
Corrected ampacity = 110 A x 0.82 = 90.2 A, about 90 A, before comparing to the termination temperature limit.
Law Reference: 2023 NEC Table 310.15(B)(1)Practice all 110 questions free — no signup required.
Related questions on this topic
- For a 112.5-kVA, 208-V, three-phase transformer with 2% impedance, what is the approximate available fault current at the secondary terminals (infinite primary)?
- A 45-kVA, 208-V, three-phase transformer has 2% impedance. What is the approximate available fault current at its secondary (infinite primary)?
- Six current-carrying THHN conductors share one raceway. If the 90 C ampacity of #6 Cu is 75 A, what is the adjusted ampacity after the fill adjustment factor for 4-6 conductors?
- A #2 Cu THHN (90 C ampacity 130 A) runs with 6 current-carrying conductors (0.80 factor) in a 40 C ambient (0.91 factor). What is the adjusted-and-corrected ampacity?
- An office has 45 general-use receptacle outlets. At 180 VA per outlet, what is the receptacle load before demand factors?
- A commercial building has a 30,000-VA receptacle load. Applying the demand (first 10 kVA at 100%, remainder at 50%), what is the demand load?