CalculationsQuestion 29 of 110
An office has 45 general-use receptacle outlets. At 180 VA per outlet, what is the receptacle load before demand factors?
a.8,100 VA
b.4,500 VA
c.9,000 VA
d.5,400 VA
Explanation
Each general-use receptacle outlet is figured at 180 VA: 45 x 180 = 8,100 VA.
Law Reference: 2023 NEC 220.14(I)Practice all 110 questions free — no signup required.