A service has 500-kcmil Cu ungrounded conductors per phase. What is the minimum copper grounded (neutral) service conductor for bonding purposes?

a.#4 AWG
b.#2 AWG
c.#1 AWG
d.1/0 AWG

Explanation

The grounded service conductor must be at least the size in Table 250.102(C)(1); for 500-kcmil Cu phase conductors that value is 1/0 Cu.

Law Reference: 2023 NEC Table 250.102(C)(1)