Services & DistributionQuestion 35 of 110

A feeder is protected by a 400-A overcurrent device. What is the minimum copper equipment grounding conductor?

a.#6 AWG
b.#4 AWG
c.#3 AWG
d.#1 AWG

Explanation

For a 400-A overcurrent device the table requires #3 Cu for the equipment grounding conductor.

Law Reference: 2023 NEC Table 250.122