Services & DistributionQuestion 32 of 110

A service uses #2/0 Cu ungrounded conductors. What is the minimum copper grounding electrode conductor?

a.#8 AWG
b.#6 AWG
c.#2 AWG
d.#4 AWG

Explanation

For service conductors over 1/0 through 3/0 Cu, the table requires a #4 Cu grounding electrode conductor.

Law Reference: 2023 NEC Table 250.66

Practice all 110 questions free — no signup required.

Related questions on this topic

Last reviewed: · editorial process

PrepPass Editorial Team · Verified against Master Electrician Licensing Exam (NEC-based) · How we review