A continuous load draws 40 A. At what minimum ampacity must the branch-circuit conductors and overcurrent device be rated?

a.50 A
b.40 A
c.32 A
d.45 A

Explanation

Continuous loads require 125% sizing: 40 A x 1.25 = 50 A for the conductors and overcurrent device.