Design & SizingQuestion 19 of 110
A roof drains 4,800 ft^2 at a design rainfall rate of 4 in/hr. Using Q = 0.0104 x A x i, what is the storm design flow?
a.150 gpm
b.250 gpm
c.200 gpm
d.320 gpm
Explanation
Q = 0.0104 x 4,800 x 4 = 199.7 gpm, about 200 gpm. Doubling the rainfall rate doubles the flow for the same roof, which is why the local 100-year rainfall intensity is critical to storm sizing. This flow selects the leader and storm drain sizes.
Law Reference: UPC §1101.0Practice all 110 questions free — no signup required.
Related questions on this topic
- A propane appliance is rated at 150,000 BTU/hr. Propane has a heating value of about 2,500 BTU per cubic foot. What is the required gas flow in cfh?
- A gas branch must deliver 55 cfh of natural gas over a 60 ft longest length. The sizing table for that length gives these capacities: 1/2 in = 42 cfh, 3/4 in = 88 cfh, 1 in = 165 cfh. What is the minimum pipe size?
- Using the rational method Q = 0.0104 x A x i, where A is the projected roof area in square feet and i is the rainfall rate in in/hr, what is the design storm flow for a 6,000 ft^2 roof at a 3 in/hr rainfall rate?
- A storm sizing table is published at 4 in/hr. A vertical leader lists a capacity of 4,600 ft^2 of roof at 4 in/hr. If the local design rate is only 2 in/hr, what roof area can that same leader serve?
- A booster pump must deliver 40 gpm and raise pressure by 45 psi. Using approximate water horsepower WHP = (gpm x psi) / 1,714, what is the water horsepower required (before pump efficiency)?
- A booster pump adds 52 psi. What is the equivalent head, in feet, that the pump develops? Use 1 psi = 2.31 ft of head.
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against Master Plumber Licensing Exam (UPC/IPC-based) · How we review