A 1,800-square-foot crawl space uses standard (non-vapor-barrier) under-floor ventilation openings. Using the common 1-to-150 ratio, what is the MINIMUM net ventilation area required?
a.About 6 square feet
b.About 18 square feet
c.About 12 square feet
d.About 1.5 square feet
Explanation
The baseline under-floor ventilation ratio is 1 square foot of net free vent area for each 150 square feet of crawl-space area. 1,800 / 150 = 12 square feet of net free area. Option a uses the reduced ratio that only applies with an approved vapor retarder. Option b overstates it. Option d divides by the wrong figure. Use 1:150 unless a code-recognized vapor barrier allows 1:1,500.
Law Reference: 2025 California Residential Code §R408.2Practice all 700 questions free — no signup required.
Related questions on this topic
- A stair section detail calls out a graspable handrail mounted 42 inches above the stair nosings. What is the BEST response during plan review?
- You are coordinating a whole-house remodel that adds a bedroom and a gas furnace. Which combination BEST reflects the required alarm coordination?
- A plan provides an attic access hatch of 20 in by 28 in for an attic that is over 30 square feet with more than 30 inches of headroom. What is the BEST correction?
- During construction you find the architectural drawings show a beam at one size but the structural drawings show a larger size for the same beam. What is the BEST first action?
- Two days before bids are due, the architect issues a document that changes the window schedule for all bidders. What is this document BEST called?
- The specifications name a specific product but add the phrase 'or equal.' A subcontractor wants to use a different brand. What is the BEST procedure?
Last reviewed: · editorial process
PrepPass Editorial Team · Verified against California CSLB General Building (B) Trade Examination · How we review