Branch Circuits & WiringQuestion 207 of 521

An 8 AWG THHN copper conductor (55 A at the 90°C column) is installed where the ambient temperature is 46–50°C. Using the 90°C correction factor of 0.82, what is the corrected ampacity?

a.55 A
b.50 A
c.45 A
d.41 A

Explanation

55 A × 0.82 = 45.1 A, rounded to 45 A. Using no correction (55 A) ignores the elevated ambient, and the other values apply the wrong factor.

Law Reference: 2023 NEC §310.15(B)