Branch Circuits & WiringQuestion 210 of 521

A 90°C-rated conductor is terminated on equipment whose lugs are listed for 75°C. Which temperature column limits the conductor's final ampacity at that termination?

a.90°C
b.75°C
c.60°C
d.55°C

Explanation

Per 110.14(C), the final ampacity cannot exceed the lowest-rated termination — here 75°C. The 90°C rating may be used only for derating math, and 60°C would apply only if the terminals were rated for 60°C.

Law Reference: 2023 NEC §110.14(C)