Branch Circuits & WiringQuestion 209 of 521

For a branch circuit rated 100 A or less, which temperature column must be used for conductor ampacity at the terminations unless the equipment or terminals are listed for a higher temperature?

a.60°C
b.75°C
c.90°C
d.Any column may be used

Explanation

Per 110.14(C)(1), for circuits 100 A or less the 60°C column applies unless the equipment/terminals are listed for 75°C (or higher). The 90°C column is never the termination limit, and you cannot freely choose the column.

Law Reference: 2023 NEC §110.14(C)