Branch Circuits & WiringQuestion 211 of 521

Under what circumstance may the 90°C ampacity column of Table 310.16 be used?

a.For final conductor sizing at the terminals
b.For the branch-circuit load calculation
c.Only for applying adjustment and correction (derating) factors
d.It may never be used

Explanation

The 90°C column serves only as the starting point for adjustment and correction factors, provided the conductor is 90°C rated. The final ampacity is still limited by the termination temperature per 110.14(C), so it cannot set the final size directly.

Law Reference: 2023 NEC §110.14(C)