Equipment & SystemsQuestion 243 of 521
A single continuous-duty 25 HP, 460 V, three-phase motor has an FLC of 34 A (Table 430.250). What minimum conductor ampacity is required for its branch circuit?
a.34 A
b.38.25 A
c.42.5 A
d.46.75 A
Explanation
NEC 430.22 requires branch-circuit conductors for a single continuous-duty motor to be sized at 125% of FLC: 34 A x 1.25 = 42.5 A. 34 A ignores the 125% factor, 38.25 A uses 112.5%, and 46.75 A uses 137.5%.
Law Reference: 2023 NEC §430.22Practice all 521 questions free — no signup required.
Related questions on this topic
- Using NEC Table 430.250, what is the full-load current (FLC) of a 10 HP, three-phase, 460-volt squirrel-cage motor?
- Per NEC Table 430.248, what is the full-load current of a 5 HP, single-phase, 230-volt motor?
- A motor's nameplate shows a full-load current of 40 A and a service factor of 1.15. Under NEC 430.32(A)(1), what is the maximum overload device rating at 125% of nameplate FLA?
- For a 20 HP, 460 V, three-phase motor (FLC 27 A), what is the maximum inverse-time circuit breaker rating for branch-circuit short-circuit and ground-fault protection, using the 250% value of Table 430.52?
- Using the same 20 HP, 460 V motor (FLC 27 A), what is the maximum dual-element (time-delay) fuse permitted by Table 430.52 for branch-circuit short-circuit and ground-fault protection?
- A 5 HP, 230 V, three-phase motor has an FLC of 15.2 A. What is the maximum nontime-delay fuse permitted by Table 430.52 for branch-circuit protection?