Equipment & SystemsQuestion 246 of 521
Using the same 20 HP, 460 V motor (FLC 27 A), what is the maximum dual-element (time-delay) fuse permitted by Table 430.52 for branch-circuit short-circuit and ground-fault protection?
a.67.5 A
b.47.25 A
c.81 A
d.33.75 A
Explanation
Table 430.52 permits a dual-element time-delay fuse at 175% of FLC: 27 x 1.75 = 47.25 A. 67.5 A is 250% (inverse-time breaker), 81 A is 300% (nontime-delay fuse), and 33.75 A is 125%.
Law Reference: 2023 NEC §430.52Practice all 521 questions free — no signup required.