Equipment & SystemsQuestion 245 of 521

For a 20 HP, 460 V, three-phase motor (FLC 27 A), what is the maximum inverse-time circuit breaker rating for branch-circuit short-circuit and ground-fault protection, using the 250% value of Table 430.52?

a.67.5 A
b.47.25 A
c.81 A
d.54 A

Explanation

Table 430.52 allows an inverse-time breaker at 250% of FLC: 27 x 2.50 = 67.5 A (then the next-standard-size rule of 430.52(C)(1) Ex. may apply). 47.25 A is 175% (dual-element fuse), 81 A is 300% (nontime-delay fuse), and 54 A is 200%.

Law Reference: 2023 NEC §430.52