For a 100 HP, 460 V motor (FLC 124 A), what minimum branch-circuit conductor ampacity does NEC 430.22 require?

a.124 A
b.136.4 A
c.155 A
d.174.6 A

Explanation

430.22 requires 125% of FLC: 124 x 1.25 = 155 A. 124 A omits the factor, 136.4 A is 110%, and 174.6 A is about 141%.

Law Reference: 2023 NEC §430.22